Product Introduction
The four-bus gas detection and alarm controller is used to detect combustible or toxic gases in the air. It supports PowerBus two-bus detectors and multi-point centralized control. The system uses a microprocessor as its control unit. When the concentration of flammable gas in the environment reaches or exceeds the preset value, the controller immediately issues an audible and visual alarm, and its relay can drive exhaust fans or other peripheral devices to help prevent explosions and fire accidents and protect lives.
The system is widely used for safety monitoring and alarm in places that require fire and explosion prevention, such as factories, oil depots, liquefied gas stations, gas stations, gas filling stations and spray booths.
Product Features
Technical Specifications
| Display Screen | 4.3-inch color screen model / black and white LCD model |
| Operation | Key operation |
| Working Voltage | AC 220 V ± 10%, 50 Hz |
| Backup Power | 24 V 1.3 Ah lead-acid battery (optional) |
| Switch Output | 4 sets of passive relay outputs, contact capacity 10 A / AC 220 V |
| Working Temperature and Humidity | -10°C to 50°C, ≤ 95% RH |
| System Power | Max. power consumption 10 W (without external equipment) |
| Number of Detectors | 4.3-inch color screen model: ≤ 30 (combustible gas); black and white LCD model: ≤ 10 (combustible gas) |
| Detector Connection | PowerBus two-wire connection |
| Data Upload | RTU standard Modbus protocol |
| Alarm Points | Two alarm levels, freely set by the user |
| Alarm Indication | Indicator light + LCD display, buzzer alarm sound |
| Installation | Fixed on-site installation, wall-mounted |
| Alarm Record Storage | Up to 2000 alarm records |
| Outer Dimensions | 245 × 340 × 90 mm |
| Cabling Specifications | 2 wires required; recommended at least RVVP 2 × 1.5 national standard shielded cable; single-core diameter ≥ 1.5 mm²; length ≤ 1000 m |
Application
Used to detect combustible or toxic gases in the air, and suitable for safety monitoring and alarm in places that require fire and explosion prevention, such as factories, oil depots, liquefied gas stations, gas stations, gas filling stations and spray booths.